Points Measured
|
Power (kW) |
|
|
Physical Points (2) |
Chiller 1 Power, Chiller 2 Power |
|
Calculated Points (1) |
Total Power
|
|
Flow (gpm) |
|
|
Physical Points (5) |
Ch 1 Evaporator and Condenser, Ch 2 Condenser,
Chilled Water Main, Second Floor Coil |
|
Calculated Points (2) |
Chilled Water Total
Ch 2 Evaporator
|
|
Temperature (deg F) |
|
|
Physical Points (8) |
Ch 1 Chilled Water Supply and Return, Ch 2 Chilled Water
Supply and Return, Ch 1 Condenser Supply and Return, Ch
2 Condenser Supply & Return |
|
Calculated Points(4) |
*Ch 1 Chilled Water Temperature Difference
*Ch 2 Chilled Water Temperature Difference
*Ch 1 Condenser Water Temperature Difference
*Ch 2 Condenser Water Temperature Difference
|
|
Differential Pressure (psid) |
|
|
Physical Points (4) |
Ch 1 Evaporator, Ch 2 Evaporator, Ch 1 Condenser, Ch
2 Condenser |
|
Load (Tons) |
|
|
Calculated Points (5) |
Ch 1 Load, Ch 2 Load, Ch 1 Condenser Load, Ch 2 Condenser Load, Total Tons
|
|
Efficiency (kW/ton) |
|
|
Calculated Points (4) |
Ch 1 Evaporator Efficiency, Ch 2 Evaporator Efficiency, *Ch 1
Condenser Efficiency, *Ch 2 Condenser Efficiency
|
Total Points: 19 physical; 16 calculated (6 not trended)
* Not trended
|