IMDS Point Name
|
Description
|
Unit
|
Location Installed
|
Sensor Type
|
Quantity
|
ch2chws
ch2chwr
ch1chws
ch1chwr
|
Chiller 1 Chilled Water Supply Temperature
Chiller 1 Chilled Water Return Temperature
Chiller 2 Chilled Water Supply Temperature
Chiller 2 Chilled Water Return Temperature
|
Deg F
|
Evaporator Supply and Return
|
10K Ohm Calibrated Thermistors
|
4
|
ch2cws
ch2cwr
ch1cws
ch1cwr
|
Chiller 1 Condenser Water Supply Temperature
Chiller 1 Condenser Water Return Temperature
Chiller 2 Condenser Water Supply Temperature
Chiller 2 Condenser Water Return Temperature
|
Deg F
|
Condenser Supply and Return
|
30K Ohm Calibrated Thermistors
|
4
|
07ccstmp
07ccrtmp
07hcstmp
07hcrtmp
|
Cold Water Cooling Coil Supply Temperature
Cold Water Cooling Coil Return Temperature
Hot Water Cooling Coil Supply Temperature
Hot Water Cooling Coil Return Temperature
|
Deg F
|
Hot and Cold water coils on 7th Floor
|
10K Ohm Thermistor
|
4
|
|
07matmp
|
Mixed Air Temperature
|
Deg F
|
Air Handler Inlet
|
10K Ohm Thermistor, 25-foot averaging sensor
|
1
|
wtroadb
wtroawb
ctroadb
ctroawb
|
Ambient Outdoor Air Drybulb Temperature
Ambient Outdoor Air Wetbulb Temperature
Cooling Tower Drybulb Temperature
Cooling Tower Wetbulb Temperature
|
Deg F
|
Weather Stations for outdoor air and at cooling tower intake
|
10K Ohm Thermistor
|
4
|
|
EWB Enclosures
|
2
|
c1vtmp
c2vtmp
|
Cooling Zone 1 Duct Average Temperature
Cooling Zone 2 Duct Average Temperature
|
Deg F
|
Cold Air Ducts
|
10K Ohm Thermistor, 8-foot averaging sensor
|
2
|
z1hvtemp
z2hvtemp
|
Heating Zone 1 Duct Average Temperature
Heating Zone 2 Duct Average Temperature
|
Deg F
|
Hot Air Ducts
|
10K Ohm Thermistor, 12-foot averaging sensor
|
2
|
z1mtmp
z1mtp2
z2mtmp
z2mtp2
|
Zone 1 Mixed Air Temperature NW
Zone 1 Mixed Air Temperatures NE
Zone 2 Mixed Air Temperature NW
Zone 2 Mixed Air Temperature NE
|
Deg F
|
Duct Supply to Zones
|
10K Ohm Thermistor
|
4
|
sz1tmp
sz2tmp
|
Zone 1 Space Temperature
Zone 2 Space Temperature
|
Deg F
|
Zones
|
30K Ohm Thermistor
|
2
|
|
ch2chflw
|
Chiller 2 Chilled Water Flow
|
gpm
|
Chilled water supply pipe between chillers, 8" pipe
|
Magnetic Flow Meter
|
1
|
|
chhdrflw
|
Chilled Water Header Flow
|
gpm
|
8" pipe to chilled water coils, before chillers
|
Insertion Vortex Flowmeter
|
1
|
|
cwhdrflw
|
Condenser Water Header Flow
|
gpm
|
10" pipe on condenser supply back to chillers
|
Insertion Vortex Flowmeter
|
1
|
oatrh
ratrh
|
Outside Air Makeup Relative Humidity to AHU
Return Air Makeup Relative Humidity to AHU
|
% RH
|
Outside air and Return Air Ducts
|
3% RH Meter
|
2
|
07hz1cfm
07cz1cfm
07hz2cfm
07cz2cfm
|
Heating Zone 1 Duct Air Flow Velocity
Cooling Zone 1 Duct Air Flow Velocity
Heating Zone 2 Duct Air Flow Velocity
Cooling Zone 2 Duct Air Flow Velocity
|
fpm
|
Zone 1 & 2 Hot and Cold Ducts
|
Hot Wire anenometer
|
4
|
|
|
7th Floor AHU Power
|
kW
|
Power Panels
|
True RMS Power Meter
|
1
|
|
|
7th Floor Lighting Power
7th Floor Plug Power
|
kW
|
Power Panels
|
True RMS Power Meter
|
2
|
|
|
MCC, CH1 and CH2 Power
|
kW
|
Power Panels
|
True RMS Power Meter
|
2
|
|
bldgkw
|
Building Main Power
|
kW
|
SMUD Utility Meter
|
Transducer
|
1
|