Points List

IMDS Point Name Description Unit Location Installed Sensor Type Quantity
ch2chws
ch2chwr
ch1chws
ch1chwr
Chiller 1 Chilled Water Supply Temperature
Chiller 1 Chilled Water Return Temperature
Chiller 2 Chilled Water Supply Temperature
Chiller 2 Chilled Water Return Temperature
Deg F Evaporator Supply and Return 10K Ohm Calibrated Thermistors 4
ch2cws
ch2cwr
ch1cws
ch1cwr
Chiller 1 Condenser Water Supply Temperature
Chiller 1 Condenser Water Return Temperature
Chiller 2 Condenser Water Supply Temperature
Chiller 2 Condenser Water Return Temperature
Deg F Condenser Supply and Return 30K Ohm Calibrated Thermistors 4
07ccstmp
07ccrtmp
07hcstmp
07hcrtmp
Cold Water Cooling Coil Supply Temperature
Cold Water Cooling Coil Return Temperature
Hot Water Cooling Coil Supply Temperature
Hot Water Cooling Coil Return Temperature
Deg F Hot and Cold water coils on 7th Floor 10K Ohm Thermistor 4
07matmp Mixed Air Temperature Deg F Air Handler Inlet 10K Ohm Thermistor, 25-foot averaging sensor 1
wtroadb
wtroawb
ctroadb
ctroawb
Ambient Outdoor Air Drybulb Temperature
Ambient Outdoor Air Wetbulb Temperature
Cooling Tower Drybulb Temperature
Cooling Tower Wetbulb Temperature
Deg F Weather Stations for outdoor air and at cooling tower intake 10K Ohm Thermistor 4
EWB Enclosures 2
c1vtmp
c2vtmp
Cooling Zone 1 Duct Average Temperature
Cooling Zone 2 Duct Average Temperature
Deg F Cold Air Ducts 10K Ohm Thermistor, 8-foot averaging sensor 2
z1hvtemp
z2hvtemp
Heating Zone 1 Duct Average Temperature
Heating Zone 2 Duct Average Temperature
Deg F Hot Air Ducts 10K Ohm Thermistor, 12-foot averaging sensor 2
z1mtmp
z1mtp2
z2mtmp
z2mtp2
Zone 1 Mixed Air Temperature NW
Zone 1 Mixed Air Temperatures NE
Zone 2 Mixed Air Temperature NW
Zone 2 Mixed Air Temperature NE
Deg F Duct Supply to Zones 10K Ohm Thermistor 4
sz1tmp
sz2tmp
Zone 1 Space Temperature
Zone 2 Space Temperature
Deg F Zones 30K Ohm Thermistor 2
ch2chflw Chiller 2 Chilled Water Flow gpm Chilled water supply pipe between chillers, 8" pipe Magnetic Flow Meter 1
chhdrflw Chilled Water Header Flow gpm 8" pipe to chilled water coils, before chillers Insertion Vortex Flowmeter 1
cwhdrflw Condenser Water Header Flow gpm 10" pipe on condenser supply back to chillers Insertion Vortex Flowmeter 1
oatrh
ratrh
Outside Air Makeup Relative Humidity to AHU
Return Air Makeup Relative Humidity to AHU
% RH Outside air and Return Air Ducts 3% RH Meter 2
07hz1cfm
07cz1cfm
07hz2cfm
07cz2cfm
Heating Zone 1 Duct Air Flow Velocity
Cooling Zone 1 Duct Air Flow Velocity
Heating Zone 2 Duct Air Flow Velocity
Cooling Zone 2 Duct Air Flow Velocity
fpm Zone 1 & 2 Hot and Cold Ducts Hot Wire anenometer 4
  7th Floor AHU Power kW Power Panels True RMS Power Meter 1
  7th Floor Lighting Power
7th Floor Plug Power
kW Power Panels True RMS Power Meter 2
  MCC, CH1 and CH2 Power kW Power Panels True RMS Power Meter 2
bldgkw Building Main Power kW SMUD Utility Meter Transducer 1