This appendix summarizes several years of utility metering
data and billing data for 925 L Street. This purpose is to
establish baseline energy use against which energy savings due
to measures taken in response to IMDS data can be evaluated.
The following data were provided to LBNL:
- Monthly gas utility bills dating back to January 1999.
Gas use by calendar month was estimated from billing months.
- Summary gas and electric data dating back to 1996 -
days per billing cycle were not included, data were of limited
use
- Monthly electric billing data from August 2000
- Monthly electric billing data for one floor that is
metered separately, dating from October 2000.
- 15-min whole-building electric demand data dating back
to 1996
- 15-min chiller demand data dating back to 1996. The
chiller power meter was installed by SMUD under a different
program. The meter was commissioned by a SMUD technician and
found to be off by a factor of 3, and the data were adjusted to
reflect this.
There are some changes that will have to be accounted for
when using the baseline data to evaluate savings:
- The 2001 energy crisis prompted some permanent
reduction measures, and could possibly have altered tenant
behavior. It was noted by the operations staff that when they
started to return lighting in some areas to previous
illumination levels, they received complaints from tenants who
still thought it was wasteful. Other than the installation of
the heat exchanger, this is the only explanatory information we
have currently for the reduction in energy use between 2000 and
2001 as seen in Figure 1.
- One floor is metered separately. The floor receives
some shared services, such as ventilation. In the past this
floor has not been occupied and only received services when
requested. The separately metered space is 12,225 (12,168
used in Enflex Calcs) square feet out of a total of 168,000.
Billing data for 2000-2002 for this floor were provided by
SMUD.
Annual Energy Use
Figure 1 shows the change in
annual energy use on the main
building meter between 1996 and 2002. Similarly, Figure 2
showns the corresponding data for the combined chiller usage.
Note that whole-building electricity use increased in 1999 at
the same time as chiller electricity use dropped. This is
likeley due to major changes in building occupancy and
schedules and a chiller replacement at that time.
Annual gas usage between 1999 and 2002 are given in Figure 3.
Gas usage increased in 2001 and 2002. From Figure 4 it is
evident that summertime gas usage has increased dramatically.
Figure 4 shows gas and electricity
use by month for the same
period.
Figure 1. Annual Energy Use by Year, Main Meter
Figure 2. Annual Chiller Energy Use by Year
Figure 3. Annual Gas Usage by Year
Figure 4. Breakdown of Total Energy Use
Weather Sensitivity
Temperature data were taken from an archive of average daily
temperatures for the city of Sacramento. This archive is
located at
http://www.engr.udayton.edu/faculty/jkissock/weather/.
Hourly temperature data were purchased from the National
Weather Service for peak demand analysis under a separate
project. The weather station is located at the Sacramento
Executive Airport. Figure 5 uses
data from University of
Dayton and Figure 6 uses the
purchased data.
Figure 5 shows the relationship
between weekday total energy
use and average outside temperature, using University of Dayton
temperature data, for 1996 to 2002. Statistically it is not a
very strong correlation; however, this is still useful in
understanding the general trend in energy usage with respect to
temperature.
Figure 6 shows a similar graph,
using only the Summer peak
hours; ie, 12-5pm, June 1 through September 30, 2000. The
"Daily Average Temperature" is thus the average of only the
hours 12-5pm. This shows a much stronger correlation, which is
expected for the warmer months. Figure 7 shows chiller
electricity use by month versus temperature.
A significant increase in summertime gas use is evident in 2001
and 2002. The reason for this is not known but warrants
further investigation. Figure 8
shows monthly gas use vs.
monthly average temperature. For the years 1999-2000, there is
a strong heating slope. The cooler months in 2001-2002 follow
the same linear trend as for 1999-2000; however, the warmer
months do not. Thus the increase in gas use is not likely due
to cooler summer temperatures.
Figure 5. Whole Building Energy vs. Outside Air
Temperature
Figure 6. Daily Peak Load vs. Outside Temperature, Summer
Peak Hours
Figure 7. Monthly Chiller Electricity Use vs. Outside
Temperature
Figure 8. Monthly Gas Use vs. Outside Temperature
Baseline and Savings Analysis
The operations staff first began to use the IMDS system in
mid-2002. At this point there has not been sufficient time to
observe the system or to expect any energy savings due to the
IMDS. In the pilot IMDS, even after a year of monitoring and
ample discovery of savings opportunities, no significant
savings were realized until after the project's end, when the
building staff upgraded the control system and began to
implement recommendations.
The 2001 data, due to California's energy crisis, may not be a
good representation of baseline operation. Using 1998 and 1999
may overestimate savings as energy use was higher in those
years. Basically a savings analysis may require a more
advanced analysis than used in evaluating the previous IMDS,
ie, it will need to adjust for other factors affecting energy
use besides temperature variations.
Cost Data
Two years of cost data were available for both electricity
and gas use. Electricity costs during this time, for peak and
off-peak periods, were relatively stable as shown in Figure 9.
In constrast, gas costs for Winter 2001 were extremely high.
This is reflected in Figure 10
and Figure 11, which give
monthly costs per kWh and per therm respectively.
Based on this data, the average annual expenditure for the main
building account is nearly $243,000, or $1.6 per square foot
per year, based on 147,750 square feet, and nearly $29,000, or
$2.4 per square foot per year, for the 12th floor, based on
12,250 square feet. Combined, the total cost is $271,000, or
$1.7 per square foot per year. On the gas side, annual costs
are $70,000, or $0.45 per square foot per year.
Figure 9. Average Utility Cost per Day, by Fuel and by
Month
Figure 10. Average Electricity Cost per kWh, by
Month
Figure 11. Average Gas Cost per Therm, by Month
Peak Loads and Demand Reduction
Since 1999, the annual/summer extreme peak loads have come
down slightly (Figure 12) and the
typical daily peak load
dropped when the chiller retrofit was completed in 1999. The
plots shown in Appendix Y summarize the past seven years of
hourly data for whole building power and chiller power. These
indicate a decrease in typical full-load operation.
In light of recent events relating to California's energy
supply, peak loads are of great interest. As part of a
separate project evaluating demand shedding programs, analysis
of peak loads at 925 L Street was done.
Figure 13 illustrates the load
reduction potential for the peak
day, June 14, in 2000 according to a ten-day baseline.
Typically these are calculated hour by hour, so this example
uses only the hour 16 (4-5pm). The demand on the peak day was
about 750 kW, and the average demand during the same hour for
the previous ten days was about 600kW. Thus, if 925 L had been
a participant in a demand shedding program and had been
requested to shed load, a 150 kW reduction would have been
necessary to meet the baseline. Any additional reduction below
the baseline would have been considered curtailment.
Note that the peak day represents an extreme situation; on
other demand reduction days, the amount of curtailment would
likely be less. Although, to our knowledge, 925 L has no
intention of participating in a demand reduction program,
pre-cooling and other peak load management strategies could be
used during extreme heat and energy usage periods.
Figure 12. Annual Peak Load by Year
Figure 13. Demand Reduction Scenario